Permit: T01MH00181

Parcel: 14115008P


Addresses:

9850 E RANKIN LP

Inspection Status: Partial Approval

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
06/13/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000*1)MOBILE HOME CONNECTION OK.2)INSTALL 100 AMP FUSES IN DISCONNECT AT TRANSFORM.3)MULTIPLE GROUNDING CONDUCTORS UNDER SINGLE LUG AT DISCONNECT.4)IDENTIFY ELECTRICAL EQUIPMENT WITH SOURCE AND LOAD.
5)MULTIPLE GROUNDING CONDUCTORS UNDER SINGLE LUG IN TRANSFORMER.
05/16/2001 MOBILE HOME ELECTRICAL Partial Approval IVRS - Inspection 0000* UNDER GROUND OK
05/15/2001 MOBILE HOME ELECTRICAL Not ready for Inspection IVRS - Inspection 0000* NOT READY