Inspection History: MOBILE HOME ELECTRICAL

Permit Number - T01MH00117

Inspection Description - MOBILE HOME ELECTRICAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/05/2001 MOBILE HOME ELECTRICAL Approved IVRS - Inspection 0000*
04/02/2001 MOBILE HOME ELECTRICAL Denied IVRS - Inspection 0999* 1) NEUTRAL NOT BONDED TO GROUND AT MAIN SERVICE. YOU NEED TO RUN A JUMPER FROM NEUTRAL TO BACK OF BOX 2) ELEC. SERVICE TO BE SECURED TO POLE WITH PROPER FITTINGS AND 1/4" LAG SCREWS 3) FUSE BOX MUST BE REPAIRED AT BOTTOM OF FUSES