Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2001 | MOBILE HOME ELECTRICAL | Approved | IVRS - Inspection 0000* ELECTRIC NOT TO BE CLEARED UNTIL PEDISTAL PASSES INSP. 1) NEUTAL NOT BONDED 2) ELECTRODE GROUNDING CONDUCTOR NOT TERMINATED AT NEUTRAL BAR 3) ELECTRODE GROUNDING CONDUCTOR NOT SECURED TO PEDISTAL |
|
| 03/13/2001 | MOBILE HOME ELECTRICAL | Not ready for Inspection | IVRS - Inspection 0000* NO ELECTRIC WORK DONE |