Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MOBILE HOME ELECTRICAL
Permit Number - T01MH00081
Inspection Description - MOBILE HOME ELECTRICAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2001 | MOBILE HOME ELECTRICAL | Approved | ||
| 06/05/2001 | MOBILE HOME ELECTRICAL | Denied | IVRS - Inspection 0999*1)ELECTRIC PEDISTAL REQUIRES SEPERATE PERMIT.2)ACORN CLUMPS ON GROUND RODS INSTALLED BACKWARD.3)GROUNDING ELECTRODE CONDUCTOR NOT PROPERLY TERMINATED IN NEUTRAL.4)GROUNDING CONDUCTOR ANDF NEUTRAL NOT BONDED IN PEDISTAL. |