Permit: T01ME00967

Parcel: 122160960


Addresses:

3540 E HAMPTON ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/11/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*ALL CORRECTED HAVE BEEN MADE.
12/14/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*FRONT OF FURNACE HAS BLOCKED ACCESS 1.) RELOCATE CONDENSATE DRAIN RUN ACROSS TOP OF FURNACE, LOCATE TRAP, ON SIDE. 2.) MAX FUSE SIZE AT UNIT LEAVE PROPERLY FUSED 40 AMPS. 3.) PROVIDE SLEEVE CONNECTOR, KNOCK OUT HOLE AT REAR OF HI VOLTAGE SWITCH AT UNIT. CORRECT/RECALL.