Permit: T01ME00857

Parcel: 123020500


Addresses:

2301 N TREAT AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T01ME00857

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2002 MECHANICAL - FINAL Approved
01/02/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) CANNOT USE GREENFIELD FLEX OUTDOORS FOR HI-VOLTAGE WIRING REPLACE WITH SEAL TITE OR EMT. 2.) NEED CONNECTOR REAR OF HI-VOLTAGE SWITCH INTO UNIT. SHARP EDGE OF HOLE IN UNIT CASING WILL CUT WIRE. 3.) TERMINATE CONDENSATE DRAINS, OK TO TERMINATE DRAINS INTO ROOF GUTTERS IF DOWN SPOUT CONTINUES DOWN TO GROUND. CORRECT/RECALL.