Permit: T01ME00800

Parcel: 12616322D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/06/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE OK FOR SHEET ROCK.
04/24/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0935*GAS PIPE IS STILL LEAKING WHAT DONT YOU UNDERSTAND? I'VE BEEN HERE 6 TIMES! PAY RE-INSPECTION FEE PRIOR TO NEXT INSPECTION A REPRESENTATIVE FROM D & H MUST BE PRESENT ON NEXT INSPECTION.
04/02/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*
04/01/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) UNIT IS OVERFUSED 2.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT SMALLER THAN 2" PAINT EXPOSED PVC W/LATEX PAINT. 3.) GAS PIPE IS LEAKING. PROVIDE A MIN 10LB. TEST ON GAS SYSTEM.
03/29/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0935*4TH VISIT STILL NO ROOF ACCESS. PAY RE-INSPECTION FEE PRIOR TO NEXT INSPECTION.
03/28/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0920*CANNOT OPEN ACCESS DOOR TO ROOF TOP. PROVIDE ACCESS & RECALL FOR INSPECTION.
02/05/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0920*NO ACCESS TO ROOF TOP.
01/11/2002 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*