Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE OK FOR SHEET ROCK. |
| 04/24/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0935*GAS PIPE IS STILL LEAKING WHAT DONT YOU UNDERSTAND? I'VE BEEN HERE 6 TIMES! PAY RE-INSPECTION FEE PRIOR TO NEXT INSPECTION A REPRESENTATIVE FROM D & H MUST BE PRESENT ON NEXT INSPECTION. |
| 04/02/2002 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/01/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) UNIT IS OVERFUSED 2.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT SMALLER THAN 2" PAINT EXPOSED PVC W/LATEX PAINT. 3.) GAS PIPE IS LEAKING. PROVIDE A MIN 10LB. TEST ON GAS SYSTEM. |
| 03/29/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0935*4TH VISIT STILL NO ROOF ACCESS. PAY RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. |
| 03/28/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0920*CANNOT OPEN ACCESS DOOR TO ROOF TOP. PROVIDE ACCESS & RECALL FOR INSPECTION. |
| 02/05/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0920*NO ACCESS TO ROOF TOP. |
| 01/11/2002 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |