Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. |
| 02/05/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*CAME TO DO FINAL INSPECTION ON CORRECTIONS MADE ON NEW SYSTEM. FOUND UNIT & DUCT HAD BEEN REPLACED. 1.) STRAP FLEX DUCT UP OFF OF DIRT MIN. 4." SPACE STRAPS MAX. 4'. 2.) INSULATE ALL BARE METAL UNDER HOME, TWYES, START COLLARS. RECALL FOR FINAL INSPECTIONS. |
| 09/13/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) GAS PIPE CANNOT RUN IN FRONT OF SERVICE ACCESS PANELS.2.) PLUMBERS TAPE IS NOT AN APPROVED METHOD FOR STRAPPING UP GAS PIPE. RECOMMEND RUNNING GAS PIPE ALONG SIDE OF ELEC. CONDUIT. RECALL FOR FINAL INSPECTION. |