Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) UNABLE TO ACCESS TOTAL HEAT PUMP CONDENSER UP AGAINST SIDE TO WALL. 2.) UNPROTECTED CONTROL WIRING EXPOSED TO SUN. 3.) MIDWEST BOX 4.) I.D FUSE FOR REMOTE SPLIT SYSTEM. 5.) ID FUSE FOR AIR HANDLER 6.) AIR HANDLER NOT PROPERLY FUSED FOR AUX. HT. STRIP 7.) COMPLETE INSULATING SUCTION LINE AT AIR HANDLER. CORRECT/RECALL FOR FINAL WHO IS MECHANCIAL CONTRACTOR. |