Permit: T01ME00601

Parcel: 133262340


Addresses:

8351 E VICKSBURG ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/23/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
07/18/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) ANCHOR ELECTRICAL DISCONNECT YOU CANNOT USE THE CONDUIT TO HOLD UP THE DISCONNECT 2.) DO NOT USE STEEL SCREWS INTO THE ROOF TO STRAP COPPER WATER LINE USE COPPER STRAPS. CORRECT & RECALL FOR INSPECTION.