Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/24/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/18/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) WHEN TERMINATING CONDENSATE OVER THE TOP OF A WASTE VENT, USE A 3/4" TIE NOT AN ELBOW AND THE VENT MUST BE MIN. 2" DIAMETER. IF YOU TERMINATE INTO THE SIDE OF A VENT USE AN APPROVED FITTING. 2.) THE VENT ON THE CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP. CORRECT & RECALL FOR FINAL INSPECTION. |