Inspection Status: Partial Approval
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2001 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) EXPOSED CONTROL WIRING SPLICES W/WIRE NUTS 2.) EXPOSED CONTROL WIRING. 3.) CONDENSATE DRAINS PVC UNPAINTED, ALREADY TURNED BROWN. 4.) INTERNAL DUCT INSULATION SUPPLY AND RETURN. WHAT TYPE INSULATION USED? SOUND LIKE BARE MTL. NO SIGN OF PINS AND CLIPS. |