Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*GAS FLEX CONNECTOR ONLY GOOD UP TO 85,000 BTU.SEE TABLE 3-D-2 1994 OR 12-7 1994 UPC FOR PROPER SIZING.CORRECT AND RECALL FOR INSPECTION. | |
| 06/20/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1)FLEX GAS LINE AT UNIT-24" CONNECTOR NOT PROPERLY SIZED FOR 100,000 BTU FURNACE.2)ALL EXPOSED CONTROL WIRING NEEDS TO BE IN APPROVED RACEWAY.3)WATER LINE AT ROOF PENETRATION-NEEDS TO BE RUN THRU CONE FLASHING.NOTE,SCREWS SECURING WATER LINE TO ROOF ARE INCORRECT.WATER LINE NEEDS TO BE BLOCKED AND CLAMPED NOT SCREWED TO ROOF!!.4)GAS LINE NEEDS CONE FLASHING AT ROOF.5)COOLER HI-VOLTAGE NEEDS PROPER MIDWEST WEATHER TITE BOX AS NECESSARY. 6)REMOVE COOLER HI VOLTAGE FROM 60 AMP/AC CIRCUIT.PROVIDE SEPARATE ISOLATED CIRCUIT AS NECESSARY. |