Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/15/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTION HAVE BEEN MADE |
| 06/12/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1)MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED, AND FUSE UNIT ACCORDINGLY.2)CANNOT TERMINATE CONDENDSATE INTO A WASTE VENT SMALLER THAN 2".RECOMMEND FLOWER BED.3)CONDENSATE DRAIN IS NOT DRAINING PROPERLY.DOES NOT HAVE ADEQUATE SLOPE.4)DO NOT USE STEEL STRAPS ON COPPER.CORRECT AND RECALL FOR FINAL INSPECTION. |