Permit: T01ME00405

Parcel: 134112840


Addresses:

8249 E BEVERLY ST

Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/12/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*1.) UNIONS ARE NOT ALLOWED IN THE GAS LINE ON THE ROOF REPLACE WITH REVERSE THREAD NIPPLE & COUPLING. 2.) PROVIDE A TRAP ON CONDENSATE DRAIN. PAINT EXPOSED PVC. W/LATEX PAINT NO SPRAY ENAMEL BLOCK & CLAMP PVC EVERY 4" 3.) CORRECTLY IDENTIFY CONDUCTORS IN DISCONNECT ON ROOF & AT CIRCUIT PANEL. GROUND WIRE SHOULD BE GREEN AT EACH END. PROVIDE PROTECTION WHERE CONDUCTORS ENTER THE EQUIPEMENT. SEAL OPENING IN BACK SIDE OF DISCONNECT.4.) EXPOSED DUCT ON THE ROOF MUST HAVE MIN 1" INSULATION. NEED ACCESS TO INSIDE HOME TO LOOK INSIDE DUCTS. NEED ACCESS TO CIRCUIT BREAKER PANEL. CORRECT & RECALL FOR INSPECTION WHEN SOMEONE WILL BE HOME.