Permit: T01ME00355

Parcel: 133360520


Addresses:

301 N BANFF AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/17/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*WORK HAS BEEN CORRECTED.
05/18/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1)3/8" GAS FLEX CONNECTOR
NOT ADEQUATE SIZE FOR 110,000.SEE TABLE 3-D-2 1994 UMC FOR PROPER SIZING.2)COPPER TUBING CANNOT COME IN CONTACT WITH STEEL STRAPS.
CORRECT AND RECALL FOR FINAL INSPECTION.
05/09/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0920* PLEASE CALL FOR AN INSP WHEN SOMEONE WILL BE HOME. THERE WAS NO MESSAGE