Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/17/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) UMC 6.509 HANG FLEX DUCT WITH 1 1/2" WIDE STRAPS MINIMUM. MAX OF 4' OC. 2) DUCT TUBE 4" OFF GROUND 3) SUPPORT FLEX CONDUIT WITHIN 12" OF TERMINATIONS AND EVEN 3' OF LENGTH 4) SUPPORT END OF GAS PIPE SO T WON'T BREAK IF SOMEONE STEPS ON IT. 5) PVC CONDUIT INTO PANEL NOT PROPERLY SUPPORTED |