Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/07/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/20/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) FUSES IN ELEC. DISCONNECT ARE TOO LARGE AT 40 AMP. 35 AMP IS MAX. CIRCUIT BREAKER ALSO. 2) IF TERMINATING CONDENSATE INTO THE SIDE OF A WASTE VENT, YOU MUST USE AN APPROVED FITTING 3) GAS PIPE AND ELEC. PENETRATIONS THRU THE ROOF REQUIRE A ROOF JACK. CORRECT AND RE CALL FOR FINAL |