Permit: T01ME00255

Parcel: 116022250


Addresses:

2751 W LEAWOOD DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/31/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
06/01/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1)INSTALL TRAP ON CONDENSATE DRAIN LINE.2)SINGLE WALL VENT CONNECTOR MUST BE MIN. 6" FROM COMBUSTIBLE INCLUDING PVC AND RUBATEX.3)CIRCUIT BREAKER AND FUSES ARE TOO LARGE-40 AMP IS MAX.CORRECT AND RECALL FOR FINAL INSPECTION.