Permit: T01ME00254

Parcel: 110050800


Addresses:

4501 E GLENN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/17/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
04/11/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1) IF TERMINATING CONDENSATE INTO THE SIDE OF A WASTE VENT, YOU MUST USE AN APPROVED FITTING
2) USE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF. 3) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 69,000 BTU. SEE TABLE 3-D-2 1994 UMC CORRECT AND RECALL FOR FINAL INSP.