Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/11/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) IF TERMINATING CONDENSATE INTO THE SIDE OF A WASTE VENT, YOU MUST USE AN APPROVED FITTING 2) USE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF. 3) GAS FLEX CONNECTOR NOT ADEQUATE SIZE FOR 69,000 BTU. SEE TABLE 3-D-2 1994 UMC CORRECT AND RECALL FOR FINAL INSP. |