Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/03/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* GAS FLEX CONNECTOR TOO SMALL DIAMETER AND TOO LONG FOR 100,000 BTU FURNACE. SEE TABLE 3-D-2 94 UPC |