Permit: T01ME00136

Parcel: 131121530


Addresses:

6241 E 31ST ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/29/2001 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* 1) CONDENSATE CANNOT TERMINATE OVER THE EDGE OF THE ROOF. TERMINATE TO WITH IN 6" OF THE GROUND.
2) INSULATE COPPER DRAIN LINE FROM STEEL UNISTRUT. CORRECT AND RE CALL FOR INSP.