Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/05/2001 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
02/16/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1) EXPOSED CONTROL WIRING ON ROOF. ENCLOSE IN SEAL TIGHT OR EMT. 2) PVC CONDENSATE PIPING REQUIRES PAINTING WITH SYNTHETIC LATEX PAINT. 3) TERMINATE OVER WET VENT WITH 3/4" TEE, NOT A 90 DEGREE ELBOW
4) MAX FUSE SIZE 30AMPS NOT 45 AMPS. LEAVE UNIT PROPERLY FUSED