Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/16/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) EXPOSED CONTROL WIRING ON ROOF. ENCLOSE IN SEAL TIGHT OR EMT. 2) PVC CONDENSATE PIPING REQUIRES PAINTING WITH SYNTHETIC LATEX PAINT. 3) TERMINATE OVER WET VENT WITH 3/4" TEE, NOT A 90 DEGREE ELBOW 4) MAX FUSE SIZE 30AMPS NOT 45 AMPS. LEAVE UNIT PROPERLY FUSED |