Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE | |
| 02/09/2001 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/31/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* USE AN APPROVED FITTING WHEN TERMINATING CONDENSATE INTO A WASTE VENT. VENT MUST BE MIN 2". VENT ON CONDENSATE DRAIN LINE UST BE DOWNSTREAM OF THE TRAP MARK DATA PLATE W/THE PROPER HEAT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY. CORRECT AND RECALL FOR FINAL |