Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RE-CONN CITY WILL NOTIFY TEP. |
| 01/17/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL BOND BUSHING ON NIPPLES WHERE USING CONCENTRIC KO'S OR REDUCING WASHERS ART 250-94 N.E.C. EW GUTTER. 2. GROUNDING ELECTRODE CONDUCTOR TO BE UNSPLICED UNLESS BY PERMANENT IRREVERSIBLE TYPE SPLICE. ART 250-64 C N.E.C |
| 01/02/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* |