Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02955
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
01/09/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
01/08/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* | |
01/07/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) BOND WATER AND GAS PIPES. 2.) 2 GROUND RODS REQUIRED 6' APART. 3.) SUPPORT RISER CONDUIT AND FEEDER CONDUIT TO GUEST HOUSE. 4.) I.D. CIRCUIT BREAKERS 5.) PERMANENT ADDRESS LABEL. 6.) I.D. NEUTRAL & GROUND WIRES. |