Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 01/14/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 01/09/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*GUEST HOUSE. 1.) SEPERATE NEUTRALS AND GROUNDS YOU WILL NEED A GROUND BAR. 2.) PLEASE PROTECT CONDUCTORS BETWEEN METER & PANEL. 3.) FITTINGS ON OUTSIDE TO BE WEATHER PROOF NOT SET SCREW. 4.) CONDUCTORS IN OPEN TRENCH ARE TO BE LISTED FOR DIRECT BURAL NOT THHN PREVIOUS INSPECTION REQUEST HAVE BEEN CORRECTED. |
| 01/08/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL GROUND BAR IN SUB PANEL MAIN HOUSE AND SEPERATE NEUTRAL & GROUNDS 2.) CHANGE 40 AMP BREAKER TO GUEST HOUSE TO 30 AMP. |