Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01EL02955
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
01/09/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*GUEST HOUSE. 1.) SEPERATE NEUTRALS AND GROUNDS YOU WILL NEED A GROUND BAR. 2.) PLEASE PROTECT CONDUCTORS BETWEEN METER & PANEL. 3.) FITTINGS ON OUTSIDE TO BE WEATHER PROOF NOT SET SCREW. 4.) CONDUCTORS IN OPEN TRENCH ARE TO BE LISTED FOR DIRECT BURAL NOT THHN PREVIOUS INSPECTION REQUEST HAVE BEEN CORRECTED. | |
01/08/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0245*1.) INSTALL GROUND BAR IN SUB PANEL MAIN HOUSE AND SEPERATE NEUTRAL & GROUNDS 2.) CHANGE 40 AMP BREAKER TO GUEST HOUSE TO 30 AMP. |