Permit: T01EL02940

Parcel: 112030760


Addresses:

3017 E RICHARDS ROW

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/18/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR.
12/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) USE SEALING LOCK NUT FOR PENETRATION ABOVE BUSS LINE. 2.) INSULATING BUSHING REQUIRED FOR CONDUCTORS #4 AND LARGER PER N.E.C. 3.) NEED TO VERIFY WATER & GAS BOND.