Permit: T01EL02917

Parcel: 11515067G


Addresses:

2245 N 13TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02917

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR SERVICE #2 OF 2. OK CABLE DROP
12/11/2001 ELECTRIC - FINAL Denied 1.) NEED TO TIE UFER TO NEUTRAL AT METER OR PANEL 2.) NEED A GROUNDING BUSHING ON INSIDE OF METER ENCLOSURE TO SERVICE PANEL.3) NEED A WATER BOND.