| 12/12/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR SERVICE #2 OF 2. OK CABLE DROP |
| 12/11/2001 |
ELECTRIC - FINAL |
|
Denied |
1.) NEED TO TIE UFER TO NEUTRAL AT METER OR PANEL 2.) NEED A GROUNDING BUSHING ON INSIDE OF METER ENCLOSURE TO SERVICE PANEL.3) NEED A WATER BOND. |