Permit: T01EL02902

Parcel: 130192180


Addresses:

4622 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/21/2002 ELECTRIC - FINAL Approved
01/10/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*SAID TO CALL JIM PRIOR TO INSP. TRIED TWICE AT 940-0081. TRIED TWICE AT 546-2097. NO ANSWER.
01/08/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*NO CORRECTIONS AS REQUESTED.
12/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*CORRECT & RECALL.1.) THE PANEL MUST HAVE A CIRCUIT INDEX OR EACH C.B. MUST BE IDENTIFIED AS TO AREA SERVED. 2.) THE ADDRESS ON THE PANEL MUST BE DURABLE AND RESISTANT TO THE AMBIENT (EATHER, SUN RAIN ETC.). USE METAL STICK ON CHARACTERS OR METAL DYMO TAPE. MAGIC MARKER" IS NOT ALLOWED. 3.) THE CIRCUIT AND CONNECTION OF THE HOT TUB MUST BE INCLUDED IN THIS PERMIT OR A SEPARATE PERMIT MUST BE SECURED. 4.) EXTENSION CORD IS NOT ALLOWED AND THE DISCONNECT SWITCH MUST BE NOT HIGHER THAN 6'7" AND NOT CLOSER THAN 5' TO THE TUB.