Permit: T01EL02893

Parcel: 120021400


Addresses:

4202 S 13TH AV

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/27/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
05/21/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
01/28/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) 2 RODE REQUIRED 6FT APART. 2.) INCORRECT RISER 3.) WILL NEED FURNACE PERMIT AND FURANCE FINALS PRIOR TO APPROVED OF SERVICE UPGRADE. 4.) MECH CONTRACTOR NOVA REFIRG. 602-488-3606. 5.) CANNOT USE GREEN PAINTED OVER AS A HOT CONDUCTOR 6.) NEED PROPER GROUNDING FOR REMOTE STRUCTURE. 7.) CANNOT USE GUTLED OUT PANEL BOARD FOR A JUNCTION BOX. 8.) CALCULATE CONDUCTOR FILL FOR THE 1' CONDUIT AND CORRECT. A REINSPECTION FEE IN DUE THE NEXT INSPECTION PLEASE HAVE LETTERHEAD AT SITE LICENSED ELECTRICAL CONTRACTOR STATING THAT COMPANY IS DOING WORK.
12/07/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*