Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 05/21/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 01/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) 2 RODE REQUIRED 6FT APART. 2.) INCORRECT RISER 3.) WILL NEED FURNACE PERMIT AND FURANCE FINALS PRIOR TO APPROVED OF SERVICE UPGRADE. 4.) MECH CONTRACTOR NOVA REFIRG. 602-488-3606. 5.) CANNOT USE GREEN PAINTED OVER AS A HOT CONDUCTOR 6.) NEED PROPER GROUNDING FOR REMOTE STRUCTURE. 7.) CANNOT USE GUTLED OUT PANEL BOARD FOR A JUNCTION BOX. 8.) CALCULATE CONDUCTOR FILL FOR THE 1' CONDUIT AND CORRECT. A REINSPECTION FEE IN DUE THE NEXT INSPECTION PLEASE HAVE LETTERHEAD AT SITE LICENSED ELECTRICAL CONTRACTOR STATING THAT COMPANY IS DOING WORK. |
| 12/07/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245* |