Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02882

Parcel: 134221310


Addresses:

6802 E 12TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/25/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*PLEASE MARK YOUR CIRCUIT BREAKERS W/AREA SERVED.
02/20/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*1.) THE GROUNDING SHOULD BE FROM MAIN PANEL NEUTRAL BAR TO GRD. ROD 1 TO GRD. ROD 2, TO COLD WTR PIPE, TO GAS PIPE. 2.) THE CONDIT UNDER THE PANEL WILL HAVE TO BE PROPERLY TERMINATED INTO MAIN PANEL. 3.) INSTALL THE RISER WIRES AND INSTALL WEATHER HEAD. TERMINATED SERVICE WIRES TO PANEL 4.) EMT CONDUIT IS NOT APPROVED FOR DIRECT BURIAL IN GROUND UNLESS IT IS FACTORY MARKED AS APPROVED FOR DIRECT BURIAL.