Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/25/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*PLEASE MARK YOUR CIRCUIT BREAKERS W/AREA SERVED. |
| 02/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215*1.) THE GROUNDING SHOULD BE FROM MAIN PANEL NEUTRAL BAR TO GRD. ROD 1 TO GRD. ROD 2, TO COLD WTR PIPE, TO GAS PIPE. 2.) THE CONDIT UNDER THE PANEL WILL HAVE TO BE PROPERLY TERMINATED INTO MAIN PANEL. 3.) INSTALL THE RISER WIRES AND INSTALL WEATHER HEAD. TERMINATED SERVICE WIRES TO PANEL 4.) EMT CONDUIT IS NOT APPROVED FOR DIRECT BURIAL IN GROUND UNLESS IT IS FACTORY MARKED AS APPROVED FOR DIRECT BURIAL. |