Permit: T01EL02873

Parcel: 132160340


Addresses:

1421 E BENSON HY


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02873

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/05/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SUPPLY SIDE. NEED GROUNDING BUSHINGS WITH JUMPERS TO CHASSIS BOTH AT BOTH PANELS. 2.) ACCURATE ADDRESS LABELS ON ALL METERS AND PEDESTALS. 3.) TIGHTEN ALL CONNECTIONS IN W. PANEL. 4.) INSTALL GRD. FROM GRD BAR TO CHASSIS OF SUB-PANEL.5.) CHANGE BREAKERS IN SUB-PANEL TO CORRESPOND WITH MANUFACTURES OF THE PANEL. SEIMENS PANCEL, USING CUTER HAMMER BREAKER.6.) AT PEDESTALS: SEPARATE GRD. & NEUTRAL CONDUCTORS. MOVE GRD CONDUCTOR TO THE CHASSIS GROUND STRIP.