Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2001 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 12/04/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) DISPOSER. THE RECEPTACLE SERVING THIS APPLIANCE IS CONCEALED BEHIND A FALSE WALL. EXTEND TO WALL SURFACE. 2.) LAUNDRY LITE. WIRING IS "EXTENSION CORD." MUST HAVE PERMANENT LISTED WIRING TO SWITCH. 3.) GROUNDED & UNGROUNDED RECEPTACLES. THESE ARE MIXED IN MOST ROOMS. IF THE WIRING SYSTEM IS UNGROUNDED THEN ONLY UNGROUNDED RECEPTACLES ARE TO BE USED. IF GROUNDED THEN ONLY GROUNDED RECEPTACLES ARE TO BE USED. 4.) INSTALL SMOKE DETECTORS IN EACH BEDROOM. 5.) THE WATER HEATER T & P DRAIN LINE IS NOT PROPERLY EXTENDED TO EXTERIOR. 6.) THE WTR.HEATER/FAU CLOSET FIRE CIELING IS DAMAGED. 7.) MSTR. BEDROOM CLOSET LIGHTS ARE IMPROPERLY WIRED WITH EXPOSED ROMEX. 8.) BATHROOMS MUST HAVE GFI RECEPTACLES 9.) KITCHEN COUNTER RECEPTACLES SERVING THESE COUNTERS MUST BE GFI TYPE. 10.) ROOM ADDITIONS, PLEASE PRESENT PROOF THE ADDED ROOMS WERE PERMITTED AND BUILT UNDER PERMITS.11.) EXTERIOR LIGHTING AND OTHER ITEMS WERE INSTALLED WITH UNPROTECTED CABLING. SOME CABLES MAY NOT BE APPROVED FOR USE IN RESIDENTIAL STRUCTURES. |