Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02870

Parcel: 134071880


Addresses:

8509 E KENYON DR

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/06/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
12/04/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) DISPOSER. THE RECEPTACLE SERVING THIS APPLIANCE IS CONCEALED BEHIND A FALSE WALL. EXTEND TO WALL SURFACE. 2.) LAUNDRY LITE. WIRING IS "EXTENSION CORD." MUST HAVE PERMANENT LISTED WIRING TO SWITCH. 3.) GROUNDED & UNGROUNDED RECEPTACLES. THESE ARE MIXED IN MOST ROOMS. IF THE WIRING SYSTEM IS UNGROUNDED THEN ONLY UNGROUNDED RECEPTACLES ARE TO BE USED. IF GROUNDED THEN ONLY GROUNDED RECEPTACLES ARE TO BE USED. 4.) INSTALL SMOKE DETECTORS IN EACH BEDROOM. 5.) THE WATER HEATER T & P DRAIN LINE IS NOT PROPERLY EXTENDED TO EXTERIOR. 6.) THE WTR.HEATER/FAU CLOSET FIRE CIELING IS DAMAGED. 7.) MSTR. BEDROOM CLOSET LIGHTS ARE IMPROPERLY WIRED WITH EXPOSED ROMEX. 8.) BATHROOMS MUST HAVE GFI RECEPTACLES 9.) KITCHEN COUNTER RECEPTACLES SERVING THESE COUNTERS MUST BE GFI TYPE. 10.) ROOM ADDITIONS, PLEASE PRESENT PROOF THE ADDED ROOMS WERE PERMITTED AND BUILT UNDER PERMITS.11.) EXTERIOR LIGHTING AND OTHER ITEMS WERE INSTALLED WITH UNPROTECTED CABLING. SOME CABLES MAY NOT BE APPROVED FOR USE IN RESIDENTIAL STRUCTURES.