Permit: T01EL02854

Parcel: 128111910


Addresses:

4818 E PASEO LUISA

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/10/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR.
12/07/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*CORRECTIONS REQUIRED 1.) THE 1ST GROUND ROD REQUIRES AN ACORN TYPE CLAMP FOR THE GROUND WIRE. THE WIRE MUST BE LOCATED ON THE OPPOSITE SIDE OF THE SCREW BOLT. 2.) THE GAS PIPE SHOULD BE BONDED ON THE HOUSE SIDE PIPE INTO WALL.3.) EACH WIRE MUST HAVE ITS OWN CLAMP DO NOT DOUBLE UP ON THE UFER AND THE COLD WATER. 4.) THE PIPE NIPPLE LOCKNUT ON THE OUTSIDE BETWEEN BOX & LD) IS INSTALLED WRONG. THE GRIPS SHOULD BE FACING (AND CUTTING INTO. CORRECT RECALL.