Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 12/07/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215*CORRECTIONS REQUIRED 1.) THE 1ST GROUND ROD REQUIRES AN ACORN TYPE CLAMP FOR THE GROUND WIRE. THE WIRE MUST BE LOCATED ON THE OPPOSITE SIDE OF THE SCREW BOLT. 2.) THE GAS PIPE SHOULD BE BONDED ON THE HOUSE SIDE PIPE INTO WALL.3.) EACH WIRE MUST HAVE ITS OWN CLAMP DO NOT DOUBLE UP ON THE UFER AND THE COLD WATER. 4.) THE PIPE NIPPLE LOCKNUT ON THE OUTSIDE BETWEEN BOX & LD) IS INSTALLED WRONG. THE GRIPS SHOULD BE FACING (AND CUTTING INTO. CORRECT RECALL. |