Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 2/10/03 AT 9:15AM OK TO CLEAR. |
| 10/08/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*NO VERIFICATION OF LICENSED CONTRACTOR. ALSO A RECONNECT PERMIT MAY BE NEED FOR POWER CLEARENCE. |
| 05/15/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |