Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 10/08/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 05/15/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) SERVICE REQUIRES 2 GROUND RODS 6' APART IN ADDITION TO A WATER LINE BOND AND A GAS LINE BOND. 3.) REMOVE ALL OLD USED WIRING UNDER PORCH AT REAR OF HOUSE 4. REINSTALL FRON PORCH FIXTURE 5. SINCE THIS IS AN UN OCCUPIED RESIDENCE, ITS A REQUIREMENT THAT A C-11 LICENSED ELECTRICAL CONTRACTOR DO THE WORK PLEASE RECALL THE INSPECTION WHEN ITEMS CORRECTED AND LEAVE A MESSAGE ON RECORDER WITH NAME IF OF LICENSED CONTRACTOR (STATE REQUIREMENT.) |