Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T01EL02840
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2001 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*OK TO CLEAR/OK CABLE DROP. | |
12/06/2001 | ELECTRIC - SERVICE UPGRADE | Denied | 1.) GROUND WIRES SHOULD BE GROUPED AND NEATLY ATTACHED TO THE WALL SURFACE.2.) EXPOSE OR INDICATE WHERE THE GAS PIPE GROUND BOND IS AT. 3.) REPLACE THE SIEMENS AND MURRAY CIRCUIT BREAKERS WITH THE TYPES INDICATED ON THE G.E. INFO TAG ON PNL. DOOR MUST BE G.E. 4.) TEP REQUIRES A MINIMUM OF 24" 2FT. OF SLACK ON THE RISER WIRES MEASURED FROM FRONT OF WEATHER HEAD. CORRECT & RECALL. |