Permit: T01EL02840

Parcel: 123121790


Addresses:

1387 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T01EL02840

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR/OK CABLE DROP.
12/06/2001 ELECTRIC - SERVICE UPGRADE Denied 1.) GROUND WIRES SHOULD BE GROUPED AND NEATLY ATTACHED TO THE WALL SURFACE.2.) EXPOSE OR INDICATE WHERE THE GAS PIPE GROUND BOND IS AT. 3.) REPLACE THE SIEMENS AND MURRAY CIRCUIT BREAKERS WITH THE TYPES INDICATED ON THE G.E. INFO TAG ON PNL. DOOR MUST BE G.E. 4.) TEP REQUIRES A MINIMUM OF 24" 2FT. OF SLACK ON THE RISER WIRES MEASURED FROM FRONT OF WEATHER HEAD. CORRECT & RECALL.