Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/21/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*PER RAY MAJUTA. WILL NEED TO BE ABLE TO PADLOCK L .B. FITTING INTO SERVICE BOX. |
| 11/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*YOU CANNOT USE AN UNLOCKED FITTING SUCH AS AN LB WHICH HAS A REMOVE ABLE COVER FOR UNPROTECTED CONDUCTORS SUCH AS UTILITY CONDUCTORS. |