Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01EL02818

Parcel: 117142640


Addresses:

560 S RUBIO AV #01


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02818

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
12/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) REMOVE OLD RISER AND ASSOCIATED EQUIPMENT 2.) NEED TO CHECK SUBPANELS FOR VERIFICATION OF WRITE UP 3.) FEEDER CONDUIT TO UNIT 560-1 COMING LOOSE 4.0 NEED TO SEE SUBPANEL #560-2.
11/28/2001 ELECTRIC - FINAL Partial Approval 1.) ALL NEUTRAL BARS HAVING A JUMPER TO ENCLOSURES AT SUB PANELS TO BE REMOVED, 2.) WATER BONDS IN EFFECTIVE BECAUSE OF PLASTIC PIPE USE 3.) SUB PANEL BY METER #1 HAS A GENERAL ELECTRIC BREAKER SIEMANS PANEL DOES NOT OK 50 AMP 4.) SEAL HOLE ABOVE ON #3 AT BOTTOM OF PANEL. 5.) STRUCTURE TO EAST OF SERVICE IS ISOLATED FROM OTHER STRUCTURE THERE FOR IT REQUIRES ITS OWN GROUNDING SYSTEM. 6.) ALL SUB PANELS TO BE ITENTIFIED ALL BRANCH CIRCUIT BREAKERS TO BE IDENTIFIED. 7.) PROVIDE A LADDER TO ROOF ACCESS.
11/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*OK TO CLEAR INCREASE FOR #1,#2 CALL FOR FINAL 2.) WHEN CHANGE OVER COMPLETE.