Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02818
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) REMOVE OLD RISER AND ASSOCIATED EQUIPMENT 2.) NEED TO CHECK SUBPANELS FOR VERIFICATION OF WRITE UP 3.) FEEDER CONDUIT TO UNIT 560-1 COMING LOOSE 4.0 NEED TO SEE SUBPANEL #560-2. | |
11/28/2001 | ELECTRIC - FINAL | Partial Approval | 1.) ALL NEUTRAL BARS HAVING A JUMPER TO ENCLOSURES AT SUB PANELS TO BE REMOVED, 2.) WATER BONDS IN EFFECTIVE BECAUSE OF PLASTIC PIPE USE 3.) SUB PANEL BY METER #1 HAS A GENERAL ELECTRIC BREAKER SIEMANS PANEL DOES NOT OK 50 AMP 4.) SEAL HOLE ABOVE ON #3 AT BOTTOM OF PANEL. 5.) STRUCTURE TO EAST OF SERVICE IS ISOLATED FROM OTHER STRUCTURE THERE FOR IT REQUIRES ITS OWN GROUNDING SYSTEM. 6.) ALL SUB PANELS TO BE ITENTIFIED ALL BRANCH CIRCUIT BREAKERS TO BE IDENTIFIED. 7.) PROVIDE A LADDER TO ROOF ACCESS. | |
11/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*OK TO CLEAR INCREASE FOR #1,#2 CALL FOR FINAL 2.) WHEN CHANGE OVER COMPLETE. |