Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/29/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 11/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CLEAN SURFACE UNDER GROUND BAR 250-12. 2.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED CONDUCTOR 250-24. 3.) BOND BOTH SERVICE 250-58. 4.) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD 5.) USE APPROVED CONNECTION AT TOP OF PANEL. 6.) LABEL BREAKER 7.) OLD DISCONNECT NOT LISTED FOR USE AS A JUNCTION BOX. |