Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/29/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR ELECT. SVC CONNECT. |
| 11/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CLEAN SURFACE UNDER GROUND BAR. 2.) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED CONDUCTOR 3.) BOND BOTH SERVICE 4.) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD. 5.) VERIFY WORK BEING DONE TO INTERIOR. |