Permit: T01EL02814

Parcel: 112072510

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/02/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/26/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*THE METAL NIPPLE GOING INTO THE STORAGE ROOM NEED TO HAVE A PLASTIC BUSHING TO PROTECT THE CABLES GOING THUR 1T-AT ITS END. 2.) OLD FUSE BOX WHERE SPLICES ARE MADE NEEDS TO BE GROUNDED THERE NEEDS TO BE A JUMPER FROM SPLICED GROUNDS TO THE BOX (BECAUSE IT METAL.)