Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02808
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/27/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) REMOVE ALL PLANTS FROM SERVICE EQUIPMENT AREA. FENCE IN WAY OF SERVICE DOOR OPENING 2.) INSTALL A SMOKE DETECTOR IN BEDROOM 3.) PERMANENTLY ADDRESS SERVICE. 4.) INSTALL DEAD FRONTS, INSTALL GROUNDING BUSHING AND BONDING JUMPER AT OFFSET NIPPLE, INSTALL KNOCK OUT SEALS 5.) SUBPANEL OVERFUSING 6.) REPLACE FEEDER CONDUCTOR TO SUB PANEL 7.) COVER GUTTER 8.) NEED A GROUND BAR TO ISOLATE SUB PANEL VIOLATION NOT LIMITTED TO ABOVE OTHER HIDDEN VIOLATION MAY EXIST. |