Permit: T01EL02808

Parcel: 138100400


Addresses:

301 E DELTA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02808

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/27/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) REMOVE ALL PLANTS FROM SERVICE EQUIPMENT AREA. FENCE IN WAY OF SERVICE DOOR OPENING 2.) INSTALL A SMOKE DETECTOR IN BEDROOM 3.) PERMANENTLY ADDRESS SERVICE. 4.) INSTALL DEAD FRONTS, INSTALL GROUNDING BUSHING AND BONDING JUMPER AT OFFSET NIPPLE, INSTALL KNOCK OUT SEALS 5.) SUBPANEL OVERFUSING 6.) REPLACE FEEDER CONDUCTOR TO SUB PANEL 7.) COVER GUTTER 8.) NEED A GROUND BAR TO ISOLATE SUB PANEL VIOLATION NOT LIMITTED TO ABOVE OTHER HIDDEN VIOLATION MAY EXIST.