Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T01EL02802
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2002 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR POWER & CABLE DROP 1.) PLEASE RECALL AFTER CROSSOVER. | |
02/12/2002 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection 0000*1.) PLEASE OND 2ND GAS SERVICE. 2.) GROUND ROD TO BE 30" IN TENCH PER CODE. 3.) PROVIDE A CONNECTOR AT BOTTOM OF PANEL FOR GROUNDS. 4.) PLEASE INSTALL RISER HUB PER MANUFACTURES REQUIREMENTS 5.) ABOVE GROUND PVC TO BE SCHEDULE 80 FOR PROTECTION FROM PHYSICAL DAMAGE. 6.) PLEASE ADDRESS PANELS NOTE 2 SERVICES. |