Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/17/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 11/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0225*BE ADVISED, THE 1999 NEC REQUIRES "ALL METALLIC PIPING ON THE PREMISES" BE GROUNDED/BOND TO THE SYSTEM GROUND. THIS INCLUDES THE GAS PIPING PLEASE BOND THE GAS PIPE TO THE COLD WATER PIPE. RECALL INSPECTION. |