Permit: T01EL02764

Parcel: 126010240


Addresses:

4220 E HOLMES ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP.
11/27/2001 ELECTRIC - FINAL Cancelled IVRS - Ri canceled
11/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) STRAP GROUPS TO BUILDING. 2) VERIFY GAS AND WATER BOND AT BUILDING. 3) PROVIDE SEALING DEVICE FOR ENTRANCE ABOVE BOSS ON SIDE. 4) NEED TO SEE JUNTION BOX ON INTERIOR TO VERIFY CONDUCTORS. 5) VERIFY PERMIT FOR A/C INSTALLATION- DISCONNECT IS INSTALLED IN AN UNSAFE MANNER.