Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 11/27/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*1.) ALL NEUTRAL BARS HAVING A JUMPER TO ENCLOSURES AT SUB PANELS TO BE REMOVED, 2.) WATER BONDS IN EFFECTIVE BECAUSE OF PLASTIC PIPE USE. 3.) SUB PANEL BY METER #1 HAS A GENERAL ELECTRIC BREAKER SIEMANS PANEL DOES NOT OK 50 AMP. 4.) SEAL HOLE ABOVE ON #3 AT BOTTOM OF PANEL. 5.) STRUCTURE TO EAST OF SERVICE IS ISOLATED FROM OTHER STRUCTURE THERE FOR IT REQUIRES ITS OWN GROUNDING SYSTEM. 6.) ALL SUB PANELS TO E ITENTIFIED, ALL BRANCH CIRCUIT BREAKERS TO BE IDENTIFIED. 7. PROVIDE A LADDER TO ROOF ACCESS. |