Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/29/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR/OK CABLE DROP. |
| 01/23/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL BUSHING OR GROMMET TO PROTECT CABLE FROM ABRAISION ON BACK OF PANEL 2.) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S 3.) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE NO MARKING PEN. MUST BE SCREWED OR RIVITED 4.) SUPPORT RISER CONDUIT WITHIN 3' OF HUB. 250-96 230-70 #9287 CITY ORDIN 300-15C NEC. |