Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR RE-CONN. |
| 11/16/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920*1.) THE SERVICE MUST HAVE AN ADDRESS ON IT NO MARKER MUST BE PERMANENT. 2.) 30 AMP BRAKER CANNOT BE DOUBLE LUGGED ALSO REMOVE RED #14 WIRE FROM 30 AMP BREAKER TO BUS 3.) PROTECT ROMEX UNDER PANEL OUTSIDE, MUST BE PHYSICALLY PROTECTED. 4.) PUT A COVER ON RECEPTACLE IN STORAGE ROOM AND PROTECT ROMEX UP TO 8' ABOVE GROUND. 5.) PUT A SMOKE DETECTOR IN BEDROOM 6.) REPLACE BROKEN COVER ON SWITCH AND RECEPTACLE IN KIT. |
| 11/15/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920* |